GUARDIAN CONTROL
SOLUTIONS
INSTRUCTIONMANUAL
IM10127
May, 2012
Safety Depends on You
Lincoln arc welding and cutting
equipment is designed and built
with safety in mind. However,
your overall safety can be
increased by proper installation
... and thoughtful operation on
your part. DO NOT INSTALL,
OPERATE OR REPAIR THIS
EQUIPMENT WITHOUT READ-
ING THIS MANUAL AND THE
SAFETY PRECAUTIONS CON-
TAINED THROUGHOUT. And,
most importantly, think before
you act and be careful.
For use with machines having Code Numbers:
JFS-C1, Guardian™ Panel
Copyright © Lincoln Global Inc.
RETURN TO MAIN MENU
Vue de la page 0
1 2 3 4 5 6 ... 79 80

Résumé du contenu

Page 1 - SOLUTIONS

• Sales and Service through Subsidiaries and Distributors Worldwide •Cleveland, Ohio 44117-1199 U.S.A. TEL: 888.935.3878 FAX: 216.383.8823 WEB 

Page 2 - MAGNETIC FIELDS

A-3INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-3SHIPPING DATATECHNICAL SPECIFICATIONS - OIL GUARDIAN™FIRE PROTECTIONGROSS WEIGHT:EXCLUDING PALLETINCLU

Page 3 - FUMES AND GASES

A-4INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-4PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - SMOKE DETECTORFIRE DETECTIONHOUSING:DIMEN

Page 4

A-5INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-5PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - HEAT DETECTOR SETFIRE DETECTIONHOUSING:DI

Page 5 - REDRESSEUR

A-6INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-6PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - SPARK DETECTOR SETFIRE DETECTIONMATERIAL

Page 6 - Thank You

A-7INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-7PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - SLIDING VALVESFIRE SUPPRESSIONMATERIAL HO

Page 7 - TABLE OF CONTENTS

A-8INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-8TECHNICAL SPECIFICATIONS - SLIDING VALVESFIRE SUPPRESSIONFIGURE – A.1CEBDATABLE – A.1 SLIDING VALVE (m

Page 8

A-9INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-9PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - SOLENOID VALVEFIRE SUPPRESSIONMATERIAL BO

Page 9

A-10INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-10TECHNICAL SPECIFICATIONS - FLAME GUARDIAN™PHYSICAL DIMENSIONS AND PROPERTIESFLAME GUARDIAN 200 FLAME

Page 10 - INSTALLATION

A-11INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-11TECHNICAL SPECIFICATIONS - GUARDIAN CONTROL™ PANELBATTERY8.0AH or 12.0AH Battery StandbyTECHNICAL SP

Page 11

A-12INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-12GENERAL DESCRIPTIONThis manual describes installation and maintenance ofcomponents for fire detectio

Page 12

FOR ENGINEpowered equipment.1.a. Turn the engine off before troubleshooting and maintenancework unless the maintenance work requires it to be running.

Page 13

A-13INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-13GUARDIAN™ CONTROL™ SOLUTIONS SYSTEMCOMPONENTSA. Spark Guardian™B. Sliding ValvesC. Spark DetectorsD.

Page 14

A-14INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-14SAFETY PRECAUTIONS• Service and Repair should only be performed byLincoln Electric Factory Trained P

Page 15

A-15INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-15SPARK GUARDIAN™GENERAL DESCRIPTIONThe Spark Guardian™ is a cyclonic Spark arrester thatprovides exce

Page 16

A-16INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-16Spark Guardian™ 10/16/20 Components (SeeFigure A.4)• Spark Guardian™, consisting of inlet(A), Cyclon

Page 17

A-17INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-173. Support the loose ends of the duct.See Figure A.8.4. Loosen all duct clamps(B).5. Slide a duct cl

Page 18

A-18INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-18NOTE: Although it is possible to mount the dustbindirectly to the Spark Guardian™, the installa-tion

Page 19

A-19INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-19SLIDING VALVESDESCRIPTIONWhen the filter system is in operation, the slidingvalves are open. In the

Page 20

A-20INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-204. Slide a connection flange (B) into both duct ends(A).5. Place the sliding valve (D in between and

Page 21

A-21INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-21FUNCTIONAL TESTING (GENERAL)NOTE: Before performing any functional testing makesure the Flame Guardi

Page 22

A-22INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-22SOLENOID VALVEDESCRIPTIONSee Figure A.18.Normally closed 3-way 2-position solenoid valve.When the co

Page 23

ARC RAYS can burn.4.a. Use a shield with the proper filter and coverplates to protect your eyes from sparks andthe rays of the arc when welding or obs

Page 24

A-23INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-23FUNCTIONAL TESTING (GENERAL)NOTE: Before performing any functional testing makesure the Flame Guardi

Page 25

A-24INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-24FLAME GUARDIAN™DESCRIPTIONThe Flame Guardian™ is a fire suppression generatordesigned to be installe

Page 26

A-25INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-252x FS-500 2x FS-500 2x FS-5001x FS-200MDB-36 MDB-48/H MDB-48/V1x FS-200 1x FS-200MDB-20 MDB-24/H MDB

Page 27

A-26INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-263. Loosely assemble mounting brackets. Hand tight-en bolts, washers and locknuts. See Figure A.24

Page 28

A-27INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-27FUNCTIONAL TESTING (GENERAL)NOTE: Before performing any functional testing makesure the Flame Guardi

Page 29

A-28INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-28GUARDIAN™ PANELDESCRIPTIONGuardian™ Panel is a fire detection panel (ULStandard 862) with a separate

Page 30

A-29INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-29FIGURE A.26 – ELECTRICAL CONNECTIONSEFABCDFJIHFIGURE A.27 – GUARDIAN CONTROL™ PANEL

Page 31

A-30INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-30All connections for field wiring are to the terminal stripsalong the top and bottom of the circuit b

Page 32

A-31INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-31MANUAL CALL POINTDESCRIPTIONManual pull station is a switch used to activate the firealarm and fire

Page 33

A-32INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-32HEAT DETECTOR SETDESCRIPTIONThe Heat Detector Set consists of two temperaturedetectors that are inst

Page 34

FOR ELECTRICALLYpowered equipment.8.a. Turn off input power using the disconnectswitch at the fuse box before working onthe equipment.8.b. Install equ

Page 35

A-33INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-33Figure A.34 shows the first heat sensor without End OfLine resistor.Alarm resistorThe heat detectors

Page 36

A-34INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-34SPARK DETECTOR SETDESCRIPTIONThere is a set of two infrared spark detectors. Thespark detectors are

Page 37

To prevent a malfunction of thespark detector, ensure that the greenearth/ground wire is properly con-nected.-----------------------------------------

Page 38

A-36INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-36FUNCTIONAL TESTING (GENERAL)NOTE: Before performing any functional testing makesure the Flame Guardi

Page 39

A-37INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-37SMOKE DETECTORDESCRIPTIONThe Smoke Detectorʼs operation is based on light scat-tering by the air sam

Page 40

A-38INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-38See Figure A.43.10. Determine the airflow direction and turn theadapter plate (A) so that the arrowe

Page 41

FIGURE A.46ABA-39INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-39• Connect the smoke detector in accordance with theElectrical Wiring Diagram using shie

Page 42

A-40INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-40TEST POINT AND INDICATORSSee Figure A.47.A. Opening for test sprayB. LED display: indicates the cont

Page 43

A-41INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-41COMMISSIONING CHECKLISTGuardian™ PanelHeat Detector Set(s)System Control PanelSpark Detector Set#Che

Page 44

A-42INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-42Smoke DetectorManual Call Point and Fire Alarm SounderFlame Guardian™Solenoid Valve#Check OK1. Is th

Page 45

PRÉCAUTIONS DE SÛRETÉPour votre propre protection lire et observer toutes les instructionset les précautions de sûreté specifiques qui parraissent dan

Page 46

A-43INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-43Sliding ValvesFinal#Check OK1. Can the ductwork carry the weight of the slid-ing valves? If not, mak

Page 47

B-1OPERATIONGUARDIAN CONTROL™ SOLUTIONSB-1SAFETYGENERALLincoln Electric does not accept any liability for dam-age to the product or personal injury ca

Page 48

B-2OPERATIONB-2GENERAL DESCRIPTIONThis manual describes installation and maintenance ofcomponents for fire detection and suppression.FIRE PREVENTION•

Page 49

B-3OPERATIONB-3GUARDIAN™ CONTROL™ SOLUTIONS SYSTEMCOMPONENTSA. Spark Guardian™B. Sliding ValvesC. Spark DetectorsD. Smoke DetectorE. Inspection Hatche

Page 50

B-4OPERATIONB-4OPERATION IN CASE OF FIREThe fire suppression system can be activated in twoways:1. Automatically by heat, sparks and/or smoke detec-to

Page 51 - OPERATION

B-5OPERATION GUARDIAN CONTROL™ SOLUTIONSB-57. Reset the panel, detectors and system controlpanel and make sure no fault indicators are lit. Ifany fa

Page 52

B-6OPERATIONB-6SOLENOID VALVESee Figure B.4.Normally closed 3-way 2-position solenoid valve.When the connected filter system is in operation, thesolen

Page 53

B-7OPERATIONB-7CONTROLThe system is designed to run in automatic mode. Inthis time-controlled operation, the system will start andstop automatically a

Page 54

B-8OPERATIONB-8• Move the “>” cursor to ʻONʼ: Press  or .• Confirm ʻONʼ: Press OK.The display shows:• Press to select the applicable time zone.

Page 55

B-9OPERATIONB-95. Press  or  to change cursor position. Press or  to change value.6. Press OK.NOTE: Timer 1 - screen 4: make sure settingPulse =

Page 56

vvThank Youfor selecting a QUALITY product by Lincoln Electric. We want youto take pride in operating this Lincoln Electric Company product •••as much

Page 57

B-10OPERATIONB-10MAIN CONTROLSMANUAL CALL POINTWhen a fire is detected, the fire detection and sup-pression system can be activated manually through a

Page 58

B-11OPERATIONB-11FIRE ACTION PROCEDUREIn case of fireWhen a fire is detected, the system can be activatedmanually through a manual call point (See Man

Page 59

B-12OPERATIONB-12Manual call point• Reset manual call point. See Reset paragraph underManual Call Point in Operation Section.ReleaseRelease of the sy

Page 60

C-1ACCESSORIESC-1OPTIONS AND ACCESSORIESThe following products can be obtained as an optionand/or accessory:GUARDIAN CONTROL™ SOLUTIONSFIGURE C.1 – OP

Page 61

D-1MAINTENANCED-1GENERAL INSTRUCTIONSIf maintenance is required for any detector, filter sys-tem or peripheral equipment, proceed as follows.1. Electr

Page 62

D-2MAINTENANCED-2GUARDIAN CONTROL™ SOLUTIONSTABLE D.1 – MAINTENANCE CALENDERITEM ACTION INTERVAL TIME INMINUTESNOTESFILTER UNIT MULTI DUST BANKDUST BI

Page 63 - ACCESSORIES

D-3MAINTENANCED-3AEROSOL DISPOSALAfter the life of the products, dispose them of in accor-dance with federal, state and local regulations.• Activated

Page 64 - MAINTENANCE

D-4MAINTENANCED-4SMOKE DETECTORThe sensor will become contaminated over time. TheLED display (See Figure D.2, Item B) shows the cur-rent degree of se

Page 65

D-5MAINTENANCED-5SPARK GUARDIAN™SAFETY• Observe the maintenance intervals given in this man-ual. Overdue maintenance can lead to high costs forrepair

Page 66

D-6MAINTENANCED-6With manual damper:1. Close the manual damper.2. Loosen the quick connect coupling (See Figure D.6,Item C) and remove dustbin.3. Clos

Page 67

viviTABLE OF CONTENTSPageInstallation...

Page 68

E-1TROUBLESHOOTINGE-1GUARDIAN CONTROL™ SOLUTIONSIf for any reason you do not understand the test procedures or are unable to perform the tests/repairs

Page 69

E-2TROUBLESHOOTINGE-2GUARDIAN CONTROL™ SOLUTIONSObserve all Safety Guidelines detailed throughout this manualIf for any reason you do not understand t

Page 70 - TROUBLESHOOTING

E-3TROUBLESHOOTINGE-3GUARDIAN CONTROL™ SOLUTIONSObserve all Safety Guidelines detailed throughout this manualIf for any reason you do not understand t

Page 71

F-1WIRING DIAGRAMSF-1GUARDIAN CONTROL™ SOLUTIONSAlarm sequence:1) Fire alarm sounder, shut down motor, close sliding valves, close solenoid valve.2) D

Page 72

F-2WIRING DIAGRAMSF-2GUARDIAN CONTROL™ SOLUTIONSX3-1 PIN to C PIN (TROUBLE ALARM)SEE LEADS ONWIRING DIAGRAM-AWIRING DIAGRAM - BX3-20 PIN to NC PIN (TR

Page 73 - WIRING DIAGRAM - A

F-3DIAGRAMSF-3GUARDIAN CONTROL™ SOLUTIONS3/2 solenoid valveSliding valve 2CAR-KITOIL FREE COMPRESSED AIRG3/8 CONNECTION PROVIDED BY END USERSliding va

Page 74 - WIRING DIAGRAM - B

NOTES GUARDIAN CONTROL™ SOLUTIONS

Page 75 - DIAGRAMS

NOTES GUARDIAN CONTROL™ SOLUTIONS

Page 76 - NOTES

WARNINGAVISO DEPRECAUCIONATTENTIONWARNUNGATENÇÃOSpanishFrenchGermanPortugueseJapaneseChineseKoreanArabicREAD AND UNDERSTAND THE MANUFACTURER’S INSTRUC

Page 77

WARNINGAVISO DEPRECAUCIONATTENTIONWARNUNGATENÇÃOSpanishFrenchGermanPortugueseJapaneseChineseKoreanArabicLEIA E COMPREENDA AS INSTRUÇÕES DO FABRICANTE

Page 78

A-1INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-1MATERIALTECHNICAL SPECIFICATIONS - SPARK GUARDIAN™FIRE PROTECTIONHOUSING (INLET + OUTLET) Powder-coate

Page 79

• Sales and Service through Subsidiaries and Distributors Worldwide •Cleveland, Ohio 44117-1199 U.S.A. TEL: 888.935.3878 FAX: 216.383.8823 WEB 

Page 80

A-2INSTALLATION GUARDIAN CONTROL™ SOLUTIONSA-2PHYSICAL DIMENSIONS AND PROPERTIESTECHNICAL SPECIFICATIONS - OIL GUARDIAN™FIRE PROTECTIONMATERIAL HOUS